Test Scenarios for Permanent-Magnet Synchronous Motor (PMSM) in TIA Portal
Aim of the Experiments: To examine the properties and behavior of a Permanent-Magnet Synchronous Motor (PMSM) under various test scenarios.
Experimental Setup – Basic Commissioning:
The experiment setup includes the following components:
·
Servo Test Unit: Control unit, Electric
servo machine, Control software: ActiveServo
·
Frequency Inverter Unit: Sinamics S120
inverter, Controlled using Siemens TIA Portal Starter App
· PC with Software Packages: TIA Portal, ActiveServo
1.
Prepare for No-Load: Ensure the
ActiveServo software is set to zero torque so the motor spins freely without
mechanical load.
2.
Enable Drive: In the TIA Portal Control
Panel, click the ON (I) button under "Drive enables" to
activate the motor.
3.
Set Initial Speed: In the
"Speed" input field, enter 200.00 rpm and press the Forward
button.
4.
Read Frequency: Navigate to the
"Actual values" section at the bottom of the panel. From the
"Further actual values" dropdown menu, select Output frequency.
At 200 rpm, this should display roughly 10.0 Hz.
5.
Iterate: Increase your speed setpoint to
reach the next frequency steps (20 Hz, 30 Hz, 40 Hz, 50 Hz). Since 10 Hz is 200
rpm, calculate and enter the subsequent speeds (e.g., 400 rpm for 20 Hz, 600
rpm for 30 Hz).
6. Record Data: At each step, record the actual output frequency and the "Speed actual value" into your spreadsheet.
Experiment 2: Measurement of Current Components id and iq
Under Different Loads
1.
Set Speed: Enter a target speed (such as
500 rpm or 1000 rpm) in the TIA Portal Control Panel and activate the motor.
2.
Set Torque: In the ActiveServo
software, select the Torque mode. Enter a desired load setting in
the torque setpoint box between 0.2 and 1.5 Nm. Click "Apply Value"
and then "Enable" to engage the active brake.
3.
Monitor Values: In the TIA Portal
"Rotate and Optimize" view, navigate to the "Further Actual
values" section. Select and observe the "Current actual value
field-generating" (id) and "Current actual value
torque-generating" (iq).
4. Record Data: For each torque setting, record the field-generating current, torque-generating current, speed, and output frequency.
Experiment 3: Determination of efficiency at different
operating points
1. Set
the Load in ActiveServo: Launch the ActiveServo software and select the Torque
mode. Enter your desired load setting in the torque setpoint box, click Apply
Value, and then click Enable to engage the active brake.
2. Navigate
TIA Portal: In the TIA Portal Project tree, expand your drive axis settings
and open the Parameterization view to access the full expert parameter
list.
3. Read
Electrical Power: Locate parameter r82 [2] ("Active power
actual value") in the list to record the system's real-time electrical
power consumption.
4. Calculate
Mechanical Power: Compute the mechanical power () manually using your
recorded torque (
) and speed (
) values with the standard rotational power formula:
5. Record
Data: Log the measured electrical power, the actual speed, the actual
torque, and your newly calculated mechanical power for each load setting.